Monitoring floating point files, Monitoring ascii files – Rockwell Automation 9323-S5500D A.I. SERIES MICROLOGIX 1000 AND PLC-500 SOFTW User Manual

Page 89

Advertising
background image

Data Table Addressing and Editing

4-21

You can use the data table monitor to change address values. To change an address

value, move to the bit or word you want to change. At the bottom of the screen, the

system indicates the address corresponding to the cursor location. Type the new value

for the bit or word, and press

[Enter]

or one of the cursor keys. The system changes

the value of the address, and displays the new value on the monitor screen.

!

Typing a value and then pressing a cursor key will cause the value to be entered in

the data table.

Monitoring Floating Point Files

Monitoring floating point files is much the same as monitoring integer files, except that

you cannot change the display radix.

Monitoring ASCII Files

When monitoring ASCII files, the file monitor screen appears as follows:

Advertising
This manual is related to the following products: