Configuration for Online Communications

15-7

3.

Press

[F2]

Interface Hardware Type

to select the interface hardware type. Refer

to the section titled

Interface Hardware Type

beginning on page

15-8

for a

description of the available interface cards and their configurable parameters.

MicroLogix 1000 A.I.

: This option is not available in MicroLogix 1000 A.I., as

the interface is automatically set to Serial Port to MicroLogix. If you are using

MicroLogix 1000 A.I. you can follow step 4 below, then turn directly to

Serial Port

to MicroLogix Controller

on page

15-21

.

4.

Press

[F3]

Online wait for reply timeout

repeatedly until the desired value is

displayed. The value will toggle from 5 to 60 in 5 second increments. This

parameter determines the length of time the program will wait for a response from

the SLC 500 or MicroLogix processor. If this value is exceeded, PLC-500 A.I. will

display an error stating that it is unable to communicate with the selected device.

The device used and the amount of traffic on the network may require that you

increase this value.

Note

A timeout error does not necessarily mean that the timeout value is too low. For

example, a disconnected cable or noisy network will generate a timeout error. A

timeout error simply indicates that the communication device sent out a packet and did

not receive a reply.

[CTL-F2]

Network Diagnostics

accesses Who functions. Network Diagnostics also

includes a function for finding RS-232 settings, which is helpful for configuring

communications. Refer to

Find Baud, Parity, Protocol Settings

on page

15-32

. More

information on Network Diagnostics is available in

Chapter 19 - Troubleshooting and

Diagnostics

.

The remaining parameters, which vary depending on the interface, are discussed on the

following pages.