MicroLogix 1000 and PLC-500 A.I. Series Software Reference

18-12

Testing and Assembling Edits

Test ladder program modifications made during an online editing session before

assembling them into the ladder program. When you test your edits, the processor

scans the edited program; executes rungs marked with insert zone markers, and ignores

rungs marked with replace or delete zone markers. This section will describe how to

test, untest, assemble, and cancel edits.

Testing Edits

Testing edits allows you to verify that the changes you entered are not going to cause

improper machine operation before you make the changes permanent.

To test edits while online:

1.

From the Top online editor menu, press

[F3]

Edit

. If edits have been made to the

program, a test option will appear on the menu bar.

2.

Press

[F8]

Test

. You will see the prompt shown on the following screen.

Command Portal keys
for this function:

.ET