Rockwell Automation 9323-S5500D A.I. SERIES MICROLOGIX 1000 AND PLC-500 SOFTW User Manual

Page 116

Advertising
background image

Ladder Program Basics

5-11

B3/10, B3/11, and B3/12 are all initially logic 0. When XIC instruction I:0/1 goes true

(e.g. because an external momentary push button closes):

Rung 1 is evaluated as false because XIC instruction B3/11 is false at this time.

Rung 2 is evaluated as true. XIC B3/11 in the branch of this rung goes true to

maintain continuity in the rung.

Rung 3 is evaluated as true.

Rung 4 is evaluated as true because XIC B3/11 has gone true. The external device

represented by OTE O:0/2 is energized.

Application:

Use this program to achieve the maintained contact action of an On-Off

toggle switch using a momentary contact push button. Press for On. Press again for

Off.

The first time you press the push button (represented by address I:0/1), instruction

B3/11 is latched, energizing output O:0/2. The second time you press the push button,

instruction B3/12 unlatches instruction B3/11, de-energizing output O:0/2. Instruction

B3/10 prevents interaction between instructions B3/12 and B3/11.

Previously, we indicated that the processor executes instructions individually, rung by

rung, to the end of the program. This is called a program

scan

and is usually repeated

many times a second. The figure below indicates in greater detail what happens during

individual scans when an external input device (represented by I:0/1) is operated.

When the state of a bit changes during the program scan, the effects this may have in

earlier rungs of the program are not accounted for until the next scan. To point this

out, we’ve shown successive scans (1000 and 1001, 2000 and 2001, etc.).

Advertising