MicroLogix 1000 and PLC-500 A.I. Series Software Reference

18-2

!

If you use DII or STI interrupts and your application requires an interrupt latency of

less than 0.50 ms, the online editing feature is not recommended. Online editing

increases the interrupt latency response time beyond 0.50 ms. To ensure that

interrupts are responded to within 0.50 ms, place the keyswitch in the RUN position.

This prevents the use of the online editing feature.

The following diagram represents the process involved in online editing.

Begin Edit

Session

Online Edit

End Edit

Session

Assemble

Edits

Test Edits

Untest Edits

Edits

complete

Edits are

unacceptable

Edits are

acceptable

Cancel Edits

Remove edits

Modify edits