Troubleshooting and Diagnostics

19-19

Output Forces

0 1

1 0

0 0

0 0

1 1

0

0

0 0

1 1

1

1 0

1

1

0

0

0 1

1 1

1 0

0 0

1 1

0

1

0 0

1 0

Data Table

O0:xx

Force
Table

Actual

Output

from

ladder

logic

to

output

devices

Output forces are written directly to the output device, and do not appear in the data

table. The value in the force table overrides the value in the data table. For example, if

O0:12 is forced to 1, it may still appear to be 0 in the data table and the ladder logic.

The actual output, and the output LED on the I/O module (if any) will be ON.

Input Forces

0 1

1 0

1 0

0 0

1 1

0

1

0 0

1 1

1

1 0

1

1

0

0

0 1

1 1

1 0

0 0

1 1

0

1

0 0

1 0

Actual

Input

Force
Table

Data Table

I1:xx

from

input

devices

to

ladder

logic

Input forces are written to the data table, and have no effect on actual input. The value

in the force table overrides the actual input. For example, if I1:12 is forced to 1, it will

appear in the data table and ladder logic as 1, regardless of the data from the actual

input device.

The force indicator LED on the SLC 500’s front panel flashes if forces are present. A

steady light indicates that forces are present and enabled.