Rockwell Automation 9323-S5500D A.I. SERIES MICROLOGIX 1000 AND PLC-500 SOFTW User Manual

Page 479

Advertising
background image

MicroLogix 1000 and PLC-500 A.I. Series Software Reference

19-48

[F5]

Tchart

run a timing chart on the highlighted address

[F7]

Dualscr

enter the dual screen mode (only available if using a high resolution
video mode. See

Programming Screen Size

in

Chapter 12 -

Customizing PLC-500 A.I.

)

[F8]

Btoggl

toggle the value of the bit under the cursor (for bit addresses only)

[F9]

Adrmode

toggle between displaying addresses and symbols

Data Entry

You can use custom data monitoring screens to change the values of addresses. The

data entry prompt for the current cell appears in the lower left corner of the screen.

To change an address value (in monitor mode):

1.

Move the cursor to the cell containing the value that you want to change.

2.

Type the new value for that address. For binary addresses, type ON, OFF, 1 or 0,

or simply press

[F8]

Btoggl

to toggle the value. Notice in the screen below that

toggling the value for bit N7:10/5 also changed the value for word N7:10.

(Compare to the screen on the previous page.)

You can also toggle between address and symbol display modes with

[F9]

Adrmode

.

Valid data entry format depends on the radix for the current cell. For example, a cell

containing an integer address formatted as BCD will interpret input as a BCD value

(e.g., 27 BCD = 39 integer).

Advertising
This manual is related to the following products: