MicroLogix 1000 and PLC-500 A.I. Series Software Reference

B-xviii

Another possibility is that the address is also used by another hardware device (such as

a video interface card), or a memory manager.

2002: NETWORK_2002

Acknowledge error - Command sent to SLC 500 wasn’t acknowledged within the wait

time set in the configuration screen.

This error usually indicates a communications failure. Check the cable connections.

Another possibility is that the network traffic is heavy and you will have to increase the

timeout value.

2003: NETWORK_2003

Receive Error. Command send to SLC 500 was acknowledged by SLC 500, but a

response to the command wasn’t transmitted in the wait time specified in the

configuration screen.

2004: NETWORK_2004

Polling Error. The SLC 500 network has been shut down due to errors on the network,

or insertion/removal of SLC 500 station on the network.

2005: NETWORK_2005

Can’t load the KT/KL Driver ‘SLC5KT.BIN’ DOS ERROR:%s

Refer to the DOS error listing beginning on page

B-ix

to interpret the DOS ERROR

number.

2006: NETWORK_2006

Specified SLC 500 station not found on the network!

Check for the following:

You may not have selected the correct station number.

The SLC 500 may have become detached from the network. For example, the

cable may be unplugged.

The SLC 500 address may have changed, either by another operator, or by the

memory having been corrupted. Use the Who Active screen to check for project

name DEFAULT at station 1.

There may be two or more devices on the DH-485 network using the same node

address.