Troubleshooting communications – Rockwell Automation 9323-S5500D A.I. SERIES MICROLOGIX 1000 AND PLC-500 SOFTW User Manual

Page 377

Advertising
background image

Configuration for Online Communications

15-41

Troubleshooting Communications

Most difficulties with serial communication involve switch settings, cabling, and

addressing.

Switch Settings

Make sure the settings you have set in PLC-500 A.I. match those set on the

communication device. Check the documentation for the communication device and

make sure the switch settings are correct.

Cabling

Many communication problems can be traced to bad connections, faulty grounding,

bent or pushed in connector pins, and other cabling problems. If your communications

are erratic, you probably have a cabling problem.

Addressing

Every station on the DH-485 or DH+ network must have a unique address. If you are

unable to communicate with a particular station, it may be that the station number is

duplicated on the network. Make sure every station has a unique address.

Communication Baud Rate

For two devices to communicate, they must use the same baud rate. The baud rate of

MicroLogix, SLC fixed, SLC 5/01, and SLC 5/02 processors is set in the status file.

The baud rate of SLC 5/03 and SLC 5/04 processors is set in channel configuration (the

baud rate will still be displayed in the status area). Any changes take effect when

power is cycled. If you lose communications when power is cycled, check the baud rate

of the SLC 500.

Advertising
This manual is related to the following products: