MicroLogix 1000 and PLC-500 A.I. Series Software Reference

2-4

MicroLogix

The MicroLogix controller provides 8 default data files (0-7) and no user-defined data

files. Data file types are listed below.

Fixed, SLC 5/01, SLC 5/02, and 5/03 OS300

The first eight data files (0-7) have default types. File 8 is reserved for future use. You

designate the file types for the remainder of the files (9-255).

SLC 5/03 OS301 and up, and SLC 5/04

The first nine data files (0-8) have default types. You designate the file types for the

remainder of the files (9-255).

Data File Types

The default data file types are:

O Output

(file 0): This file stores the state of the output terminals for the

controller.

I Input

(file 1): This file stores the status of the input terminals for the controller.

S Status

(file 2): This file stores controller operation information. This file is

useful for troubleshooting controller and program operation.

B Binary or Bit

(file 3): This file is used for internal relay logic storage.

T Timer

(file 4): This file stores the timer accumulated and preset values and

status bits.

C Counter

(file 5): This file stores the counter accumulated and preset values and

the status bits.

R Control

(file 6): This file stores the length, pointer position, and status bits for

specific instructions such as shift registers and sequencers.

N Integer

(file 7): This file is used to store numeric values or bit information.

Values range from -32768 to 32767.

F Floating Point

(file 8): Only SLC 5/03 OS301 and SLC 5/04 OS400 processors

and higher use floating point. This file stores single precision non-extended 32-bit

numbers. The valid range is

±

1.1754944e

-38

to

±

3.40282347e

+38

.