background image

Data Table Addressing and Editing

4-25

Multipoint Monitoring

(SLC 5/03 OS302, 5/04 OS401, and MicroLogix only)

Multipoint monitoring allows

you to define a list of bit addresses for monitoring and editing. These addresses need

not be contiguous. You can use a multipoint list to:

change the on/off state of bits

set and clear forces on I/O points

define symbols

write protect a bit

The multipoint list for SLC 5/03 OS302 and 5/04 OS401 processors can contain as

many as 32 points. The multipoint list for MicroLogix controllers can contain only 16

points. Two modes are available, Online and Offline. The multipoint display and

menus are slightly different between the two modes. The online multipoint list is

stored in the processor’s memory and is, therefore, cleared whenever the processor’s

memory is cleared. The offline multipoint list is stored in the project file. It is not part

of the processor image; however, you can add it to the processor image by copying it to

the online multipoint list.

To access the multipoint list in

PLC-500 A.I.

:

1.

From the top menu of the ladder editor, press

[F8]

Display

.

2.

Select

[F9]

Custom

. A box like the following will appear on the screen.

Command Portal keys
for this function: