Online Editing and Monitoring

18-21

Message

Description

Recommended Action

AB Compiler error - 3:

Out of memory in
processor image.

Transfer of an accepted rung to
a SLC 5/03 or 5/04 failed
because there is not enough
program space for the selected
rung size in the processor.

Reduce or optimize your
user program or perform
offline editing.

Can’t acquire edit
resource!

Online editing is not allowed
when the SLC 5/03 or 5/04
keyswitch is in the Run position.

Change the keyswitch to the
REM or PROG position.
Retry the function.

Switch back to
RemRun mode?

The processor mode is being
changed from REMprog to
REMrun.

Make sure it is safe to place
the processor into REMote
run mode and execute the
program.

Warning! The SLC’s
program has been
modified by another
computer! Program
must be re-read!

Only one terminal may be
online when edits are being
performed. (Multiple terminals
can be online at the same time,
but you can only monitor ladder,
no edits are allowed.)

Remove one of the terminals
from the online mode.

Note

Error 001F (Program Integrity Problem) occurs if a problem was detected in the edited

program. You must re–download your program and then re-enter your edits.