A network example – Rockwell Automation 9323-S5500D A.I. SERIES MICROLOGIX 1000 AND PLC-500 SOFTW User Manual

Page 338

Advertising
background image

MicroLogix 1000 and PLC-500 A.I. Series Software Reference

15-2

A Network Example

The diagram on page

15-4

shows an example of an extended network that uses DH-

485, DH+, and Ethernet®. Numbers 1 to 6 in the diagram correspond to the following

descriptions:

1.

Terminal on DH–485 Network.

The first section of the table on page

15-9

indicates the methods you can use to connect a programming device to the DH–485

network.

2.

DH–485 Network.

The network can extend to a maximum length of 4000 ft

(1,219.2 m). The valid node address range is 0 - 31 decimal. The diagram shows

a 1747–AIC link coupler at each network drop. The interface device can be

connected to any of the link couplers (A, B, C, or D).

The diagram shows a processor (SLC 5/01, SLC 5/02, and SLC 5/03) connected to

three of the link couplers. The link couplers are powered by the processors. Note

that the fourth link coupler (at the left) does not have a processor connected to it.

For this reason, it is energized by a 24 VDC power supply, 1747–NP1 (or 1747–

NP2).

The DH–485 network extends downward on the right to a 1785–KA5 gateway

module. This gateway module is required only when you have a terminal on a

DH

+

network from which you want to communicate with devices on the DH–485

network. The gateway module has a node address (0 to 31 decimal) on the DH-485

network, as well as a DH-485 link id.

3.

Terminal on DH

+

Network.

This terminal is connected to an interface device,

which connects the programming device to the DH

+

network. With the A.I. Series

software installed, the programming device communicates with devices on the

DH

+

network. For DH–485 network communication, a 1785–KA5 Gateway

module is required.

Advertising
This manual is related to the following products: