18-19

Program Mode Online Editing Effects

Action

Effect of Edit

Insert a rung

Insert zone markers appear while editing the rung. The markers are
removed when you accept the rung.

Delete a rung

Normal rung

: The rung is removed.

Insert rung

: The rung is removed.

Delete rung

: The rung is removed.

Replace rung

: Not allowed. Only the insert rung of an “I/R” pair can

be edited.

Insert rung of “I/R” pair

: The insert rung is removed. The replace

zone markers are removed from the replace rung and the rung is
displayed as a normal rung.

Modify a rung

Normal rung

: The original rung is marked with a replace zone marker

and a copy is created above it and marked with an insert zone
marker. You can only modify the insert rung.

Insert rung

: The rung is modified. An “I/R” pair is created only until

the rung is accepted.

Delete rung

: Not allowed. A message appears stating that you

“Cannot Edit this rung!”

Insert rung of “I/R” pair

: The insert rung is modified. The replace

rung is unchanged.

Replace rung

: Not allowed. Only the insert rung of an “I/R” pair can

be edited.

Undelete a rung Inserts the previously deleted rung from the buffer as a normal rung

above the current cursor location.

Assemble edits

Replace and delete rungs are removed. Insert rungs remain, but the
edit zone markers change to normal rungs.

Cancel edits

Insert rungs are deleted. Replace and delete rungs remain, but the
edit zone markers change to normal rungs.

Test edits

These two options are only available if the program contains edit

Untest edits

zones from a run mode online editing session that were not tested
and assembled. The effect is the same as for run mode online
editing.