MotionSuite™ Series Machine Controller Software Manual

Chapter 7: System Data Definition

7-33

5. Retention of Previous High-Scan Input Value

Input the number of times the previous value of the high-speed scan input is held
upon occurrence of an I/O error. For example, if “3” is input, the high-speed
scan input is reset after four continuous I/O error occurrences. Input a value
within the range of 1 ~ 255 for the Previous Value Hold Designation High-Speed
Input.

6. Retention of Previous Low-Scan Input Value

Input the number of times the previous value of the low-speed scan input is held
upon occurrence of an I/O error. For example, if “3” is input, the low-speed scan
input is reset after four continuous I/O error occurrences. Input a value within
the range of 1 ~ 255 for the Previous Value Hold Designation Low-Speed Input.

7. Interlock at Module Replacement

Set whether the interlock at module is valid or invalid according to the applica-
tion program.

8. System Software Number

Displays the PLC system software number.

9. Running Status

This displays the running status of the current PLC in the on-line mode. The
meaning of the various displays is shown in Table 13. Care must be taken as the
number of LEDs on the front of the PLC differ. For details on the various run-
ning statuses, see the appropriate user’s manual for the machine controller used.

10. Start-up Status

This shows the status when the PLC starts.

11. Power Up Status

This displays the status when power returns.

Table 13: Running Statuses

Status

Meaning

READY

ON: Normal
OFF: Self-diagnosis error

ON when the module is normal, OFF during self-diagnosis
errors.

RUN

ON: Running
OFF: Run Stop

ON when on-line (scan processing execution). OFF on occur-
rence of fatal error/PLC run stop operation in System Config-
uration window.

ALARM

ON: Alarm
OFF: Normal

ON during alarm, OFF when normal

ERROR

ON: Error
OFF: Normal

ON during error, OFF when normal

BAT ALM

ON: Battery voltage drop
OFF: Battery voltage normal

ON when battery voltage drops, OFF when normal

BUS
ACCESS

ON: Bus Access
OFF: Bus access stop

ON during bus module access, OFF during bus access stop.