MotionSuite™ Series Machine Controller Software Manual

Chapter 8: Ladder Programming

8-68

3. Input: Register

Input the register number to be input. The current values are displayed in the on-
line mode.

4. Input: Unit

Input units of registers to be input in 8 16-bit characters (4 32-bit characters) or
less. 16-bit and 32-bit characters can be combined in this entry.

5. Setting Range: Lower Limit

Input the value to be used in the lower limit check following scale conversion.

6. Setting Range: Upper Limit

Input the value to be used in the upper limit check following scale conversion.

7. Scale Conversion Designation/Bit Signal Conversion Set

Input the conversion format for the register values input. Leave a 16-bit space
between the value and the operations of the format which is input.

8. Output: Symbol

Input a symbol pertaining to the register number output in 8 16-bit characters (4
32-bit characters) or less. 16-bit and 32-bit characters can be combined in this
entry.

9. Output: Register

Input the output register number storing the converted value of the registers
which were input.

10. Output: Unit

Input units of registers to be output in 8 16-bit characters (4 32-bit characters) or
less. 16-bit and 32-bit characters can be combined in this entry.

Note:

Input registers and output registers must be set. An error occurs during storage if these
are not set.

Note:

User function I/O conversion tables cannot be created.

8.3.6

Interlock Table Data Input

Various interlock conditions are defined in interlock tables. Interlock conditions are
defined by inputting symbols, bit-form register numbers, and signal types (normally
open contact, normally closed contact, coil). Upon storing this table, it becomes a sub-
program configured from the normally open contact, normally closed contact, and
coil. The sub-program is referred to from the main program XCALL command.