16

Parameter reference

16.2

Parameter list | C01235

1004

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C01235

C01236

C01237

Parameter | Name:

C01235 | MCK: Manual jog waiting times

Data type: UNSIGNED_16

Index: 23340

d

= 5B2C

h

Waiting times for manual jog

Manual jog

Setting range

(min. value | unit | max. value)

0.000

s

65.000

Subcodes

Lenze setting

Info

C01235/1

5.000 s

Manual jog: Waiting time 2nd speed

• Time after which the first manual speed (

C01231/1

) is

accelerated to the second manual speed (

C01231/2

).

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C01236 | MCK: Speed follower

Data type: INTEGER_32

Index: 23339

d

= 5B2B

h

Speeds for position follower

Position follower

Setting range

(min. value | unit | max. value)

-214748.3647

units/s

214748.3647

Subcodes

Lenze setting

Info

C01236/1

360.0000 units/s

PosFollower: Sync. speed

• Synchronisation speed for approaching the setpoint

position of the master.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10000

Parameter | Name:

C01237 | MCK: Acceleration follower

Data type: INTEGER_32

Index: 23338

d

= 5B2A

h

Accelerations for position follower

Position follower

Setting range

(min. value | unit | max. value)

-214748.3647

units/s2

214748.3647

Subcodes

Lenze setting

Info

C01237/1

720.0000 units/s2

Pos follower: Sync. accel.

• Acceleration for ramp-up to synchronisation speed.

C01237/2

720.0000 units/s2

Pos follower: Sync. decel.

• Deceleration for synchronisation speed ramp-down

to standstill (to the setpoint position of the master).

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10000