263

5

Motor control (MCTRL)

5.11

Encoder/feedback system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.11.4

Encoder with HTL level at DI1/DI2

Low speeds (except for edge counting)
For the first three methods (

C00496

= 0, 1, or 2), the minimum speed that can be measured depends

on the encoder resolution.
The quantisation error

• is independent of the encoder resolution,
• exclusively depends on the encoder quality (encoder errors).
• at least amounts to 0.5 rpm.

Internal arithmetic operations automatically maintain the minimally required value of the scanning

time in order to achieve maximum dynamics.

Note!

At the digital terminals DI1 and DI2, only encoders with HTL level can be used.
In spite of the selected operating mode without encoder feedback, the actual speed

value (

C00051

) is calculated if an encoder is connected and "1: Encoder signal FrqIn12" is

selected in

C00495

.

Encoder

resolution

(Number of

increments)

Min. measurable speed in [rpm]

8

16

16

8

32

4

64

2

128

1

256

0.5

512

0.25