Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

135

5

Motor control (MCTRL)

5.1

Motor selection/Motor data

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

• Care must be taken that the constant mass inertia of the drive (mass inertia of motor, gearbox,

shaft and constant load) is entered as exactly as possible in

C00273

to calculate the speed

controller parameters as dynamically as possible.

• Mass inertias that are not constant (e.g. changing loads of reels or different loads of hoists)

must be entered in

C00919/1

.

• If the mass inertia set in

C00273

is too low, the speed controller parameters are calculated

less dynamically.

• If the mass inertia set in

C00273

is too high, speed controller operation is unstable.

• If the mass inertia in

C00273

is set to "0", the setting of bit 5 in

C02865/1

has no effect on the

speed controller parameter calculation. In this case, the speed controller parameters will not be

calculated automatically after motor parameter identification.

Automatic calculation of other controller parameters

From version 12.00.00 onwards:

Following successful motor parameter identification, the controller

parameters listed in the below table can also be calculated automatically.

• If these parameters are to be calculated, bit 6 of

C02865/1

must be set to "6".

Selection of the identification mode

From version 12.00.00 onwards

, two identification modes are available in

C02867/1

:

• "1: Basic identification" (previous mode)

• Only for asynchronous motors
• Duration approx. 30 s

• "2: extended identification"

• Stands out due to increased accuracy of the determined motor parameters.
• Also supports synchronous motors and asynchronous motors with a power of more than 11

kW.

• Duration approx. 80 s

Tip!
In the Lenze setting, a setting of "0: automatic" is selected in

C02867/1

. This setting ensures

that the controller automatically selects the optimum procedure for motor parameter

identification.

Parameter

Info

ASM

PSM

C00011

Appl.: Reference speed

C00022

Imax in motor mode

C00497

Nact filter time constant

C00966

VFC: Time const. slip comp.

C00982

VFC-ECO: Voltage reduction ramp