C00682 | l_compare_1: window, C00685 | l_compare_2: fct, C00686 | l_compare_2: hysteresis – Lenze 8400 User Manual

Page 875: C00687 | l_compare_2: window, C00682, 16 parameter reference

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

875

16

Parameter reference

16.2

Parameter list | C00682

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00682

C00685

C00686

C00687

Parameter | Name:

C00682 | L_Compare_1: Window

Data type: INTEGER_16

Index: 23893

d

= 5D55

h

The

L_Compare_1

FB: Window for the comparison function selected in

C00680

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

100.00 2.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00685 | L_Compare_2: Fct.

Data type: UNSIGNED_8

Index: 23890

d

= 5D52

h

The

L_Compare_2

FB: Comparison operation

• If the statement of the selected comparison operation is true, the binary bOut output will be set to TRUE.

Selection list

(Lenze setting printed in bold)

1 In1 = In2
2 In1 > In2
3 In1 < In2
4 |In1| = |In2|
5 |In1| > |In2|
6 |In1| < |In2|

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00686 | L_Compare_2: Hysteresis

Data type: INTEGER_16

Index: 23889

d

= 5D51

h

The

L_Compare_2

FB: Hysteresis for the comparison function selected in

C00685

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

100.00 0.50 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00687 | L_Compare_2: Window

Data type: INTEGER_16

Index: 23888

d

= 5D50

h

The

L_Compare_2

FB: Window for the comparison function selected in

C00685

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

100.00 2.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100