16

Parameter reference

16.2

Parameter list | C00634

868

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00634

C00635

C00636

Parameter | Name:

C00634 | L_NSet_1: wState

Data type: UNSIGNED_16

Index: 23941

d

= 5D85

h

The

L_NSet_1

FB: Bit coded status display

Display area

(min. hex value | max. hex value)

0x0000

0xFFFF

Value is bit-coded:

Info

Bit 0 No blocking zone active

"1" ≡ No blocking zone set for constant speeds

Bit 1 Blocking zone 1 active

"1" ≡ Suppression of constant speed characteristics

within the limits of blocking zone 1

Bit 2 Blocking zone 2 active

"1" ≡ Suppression of constant speed characteristics

within the limits of blocking zone 2

Bit 3 Blocking zone 3 active

"1" ≡ Suppression of constant speed characteristics

within the limits of blocking zone 3

Bit 4 Jog in blocking zone

"1" ≡ A ramp is used to keep the speed setpoint within a

speed blocking zone

Bit 5 MaxLimit active

"1" ≡ Speed setpoint is at the maximum speed limit

Bit 6 MinLimit active

"1" ≡ Speed setpoint is at the minimum speed limit

Bit 7 Reserved
Bit 8 Reserved
Bit 9 Reserved

Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C00635 | L_NSet_1: nMaxLimit

Data type: INTEGER_16

Index: 23940

d

= 5D84

h

The

L_NSet_1

FB: Maximum speed setpoint for speed setpoint limitation

Setting range

(min. value | unit | max. value)

Lenze setting

-199.99

%

199.99 199.99 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00636 | L_NSet_1: nMinLimit

Data type: INTEGER_16

Index: 23939

d

= 5D83

h

The

L_NSet_1

FB: Minimum speed setpoint for speed setpoint limitation

Setting range

(min. value | unit | max. value)

Lenze setting

-199.99

%

199.99 -199.99 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100