Motor control (MCTRL)

5.1

Motor selection/Motor data

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

How to carry out automatic motor parameter identification:

1. Inhibit the controller if it is enabled, e.g. via the

C00002/16

device command or a LOW

signal at the X5/RFR terminal.

• For executing the motor parameter identification, the controller must be in the

"

SwitchedOn

" status.

2. Wait until the drive is at standstill.
3. Ensure that a motor control suitable for the motor is set in

C00006

.

4. Transfer the nameplate data to the following codes:

C00081

: Rated motor power

C00087

: Rated motor speed

C00088

: Rated motor current (according to the connection method /)

C00089

: Rated motor frequency (according to the connection method /)

C00090

: Rated motor voltage (according to the connection method /)

C00091

: Motor cos ϕ

5. Defining the motor cable length and motor cable cross-section:

C00915

: Motor cable length

C00916

: Motor cable cross-section

The resulting motor cable resistance is displayed in

C00917

.

6. Activate motor parameter identification via the

C00002/23

= "1: On / start" device

command.

7. Enable the controller again.

• The controller changes to the "

Ident

" device status.

• Motor parameter identification starts.
• The progress of the identification run can be seen in

C00002/23

.

• The identification is completed if the "0: Off / ready" message is displayed in

C00002/23

.

• After successful identification, it changes back to the "

SwitchedOn

" device status.

8. Inhibit controller again.