Sd11: Speed limit for feedback system 67 [xx.0123.00201]

Sd3: Open circuit - feedback system [xx.0123.00205]

An01: AIN1_I < 4 mA [xx.0125.00001]

An02: AIN2_I < 4 mA [xx.0125.00002]

Io11: DigOut level [xx.0125.00011]

Response (Lenze setting printed in bold)

Setting:

C00607

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Maximally permissible speed of the feedback system

connected to DI6/DI7 reached.

Reduce speed of the rotation shaft/feedback system.

n

encoder

<= (f

max

x 60) / encoder increment

(for f

max

= 10 kHz)

Response (Lenze setting printed in bold)

Setting:

C00586

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

• HTL encoder cable interrupted.

• HTL encoder is defective.

Note: May also be caused by a very dynamic acceleration

or starting up against a blocked motor shaft (e.g. with a

closed holding brake).

• Check HTL encoder cable.

• Check HTL encoder.

• Check related terminals.

• Switch off monitoring (

C00586

= "0: No reaction")

when the HTL encoder is not used.

Response (Lenze setting printed in bold)

Setting:

C00598/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Open-circuit monitoring for analog input 1 has tripped.

• Only if the analog input has been configured as a

current loop of 4 ... 20 mA (

C00034/1

= 2).

• Check wiring of the analog X3/A1I input terminal for

open circuit.

• Check minimum current values of the signal sources.

Response (Lenze setting printed in bold)

Setting:

C00598/2

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Open-circuit monitoring for analog input 2 has tripped.

• Only if the analog input has been configured as a

current loop of 4 ... 20 mA (

C00034/2

= 2).

• Check wiring of the analog X3/A2I input terminal for

open circuit.

• Check minimum current values of the signal sources.

Response (Lenze setting printed in bold)

Setting:

C00598/3

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The actual level of a digital output does not correspond

to the setpoint level.

• Check wiring of the digital output terminal for short

circuit to earth.

• Check whether the digital output terminal is by

mistake triggered externally with a HIGH signal

although a LOW signal should be output.