C00425 | encoder scanning time, C00426 | ssi encoder: data bits, C00425 – Lenze 8400 User Manual

Page 825: C00425/1, C00425/2, C00426/1, C00426/2, C00426/3, C00426/4, C00426/5

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

825

16

Parameter reference

16.2

Parameter list | C00425

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00425

C00426

Parameter | Name:

C00425 | Encoder scanning time

Data type: UNSIGNED_8

Index: 24150

d

= 5E56

h

Encoder sample time for the digital input terminals when configured as frequency inputs

Using DI1(5) and DI2(6) as frequency inputs

Selection list

0 1 ms
1 2 ms
2 5 ms
3 10 ms
4 20 ms
5 50 ms
6 100 ms
7 200 ms
8 500 ms
9 1000 ms

Subcodes

Lenze setting

Info

C00425/1

3: 10 ms

FreqIn12: Encoder scanning time

C00425/2

3: 10 ms

FreqIn56: Encoder scanning time

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00426 | SSI encoder: Data bits

Data type: UNSIGNED_8

Index: 24149

d

= 5E55

h

From version 02.00.00

Example: Setting for an SSI encoder with coding "8192x4096":

• 8192 = 2

13

= 13 bits multiturn  C00426/4 = 13

• 4096 = 2

12

= 12 bits singleturn  C00426/2 = 12

• This results in a data word length of 25 bits  C00426/1 = 25

• Start bit singleturn = bit 0  C00426/3 = 0

• Start bit multiturn = bit 12  C00426/5 = 12

Encoder/feedback system: SSI encoder

Setting range

(min. value | unit | max. value)

0

32

Subcodes

Lenze setting

Info

C00426/1

25

SSI encoder: Data word length

C00426/2

13

SSI encoder: Bits SingleTurn

C00426/3

0

SSI encoder: Start bit Singleturn

C00426/4

12

SSI encoder: Bits Multiturn

C00426/5

13

SSI encoder: Start bit Multiturn

C00426/6

0

SSI encoder: Status bit

From version 12.00.00

C00426/7

6

SSI encoder: Left shift of raw value

From version 12.00.00

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1