I-1600, 11 canopen option – Lenze 8400 User Manual

Page 691

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

691

11

CANopen option

11.11

Implemented CANopen objects | I-1600

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

I-1600

The object I-1600 serves to receive parameter data as RPDO1.

• This object relates to codes

C00409/1...4

and

C00866/1...4

.

From version 12.00.00 onwards:

For 32-bit values, this object relates to codes

C00407/1...2

.

[11-14] Data telegram assignment

IEC 61131 process data words are mapped. Only whole bytes can be mapped (1-byte/mapping

entry).

Related topics:

RPDO1 | Port block "LP_CanIn1"

( 646)

Index:

I-1600

Name:

RPDO1 mapping parameter

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Number of mapped application

objects in PDO

0

0

8 rw

U8

1 ... 4: Application object 1 ... 4

0

0

4294967295 rw

U32

Subindex

Meaning

0

Number of mapped objects

1 ... 4

Mapping entries 1 ... 4 for RPDO1

• The 4th mapping entry is used for the statistic mapping. For this, there is no value

available.

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31 ... bit 16

Bit 15 ... bit 8

Bit 7 ... bit 0

Index

Subindex

Length

Advertising