97 l_limit_1, 97 l_limit_1 8, L_limit_1 – Lenze 8400 User Manual

Page 1308: 18 function library

Advertising
background image

18

Function library

18.1

Function blocks | L_Limit_1

1308

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

18.1.97

L_Limit_1

This FB limits an analog input signal to a value range whose upper and lower limit can be set via

parameters.

Inputs

Outputs

Parameter

Tip!
Always set the lower limit lower than the upper limit, otherwise value "0" is provided at the

nOut_a output.

Identifier

Data type

Information/possible settings

nIn_a

INT

Input signal

• Scaling: 16384 ≡ 100 %

Identifier

Data type

Value/meaning

nOut_a

INT

Output signal

• Scaling: 16384 ≡ 100 %

Parameter

Possible settings

Info

C00630/1

-199.99

%

199.99 Lower limit

• Lenze setting: -100.00 %

C00630/2

-199.99

%

199.99 Upper limit

• Lenze setting: 100.00 %