6 enable controller and test application, Enable controller and test application, 3commissioning – Lenze 8400 User Manual

Page 76

Advertising
background image

3

Commissioning

3.8

Commissioning of the "Table positioning" technology application

76

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.8.5

Saving parameter settings safe against mains failure

The parameter set must be saved to the device safe against mains failure to prevent parameter

settings becoming lost due to mains switching.

Save parameter set.

3.8.6

Enable controller and test application

1.

Enable controller

• If there is no other active source for the controller inhibit, the controller changes from the

"

SwitchedOn

" status to the "

OperationEnabled

" status.

• The Diagnostics tab and

C00158

display all active sources for the controller inhibit.

2. Select the respective control signals via the digital inputs (see sections below).

Homing

1. Requesting the "Homing" operating mode:

• Set digital input DI5 to LOW level to select profile 1 and at the same time request the

"Homing" operating mode..

2. Start homing:

• Set digital input DI6 to HIGH level ("Alternative function PosExecute").

3. Conclude homing when homing position has been reached:

• Reset digital input DI6 to LOW level.

Stop!

Before stipulating a speed setpoint, check whether the brake in the form of a holding

brake on the motor shaft has been released!

Note!

Observe the actual speed value (display in

C00051

) as well as the

LED status displays

.

( 554)