C02865 | mctrl: special settings, C02865/1, Bit 6 of – Lenze 8400 User Manual

Page 1066: Has no effect on the, Must be set, C2865/1, C02865, 16 parameter reference

Advertising
background image

16

Parameter reference

16.2

Parameter list | C02865

1066

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C02865

Parameter | Name:

C02865 | MCTRL: Special settings

Data type: UNSIGNED_16

Index: 21710

d

= 54CE

h

From version 12.00.00

Activation of special functions of the internal motor control
Setting range

(min. hex value | max. hex value)

0x0000

0xFFFF

Value is bit-coded:

Info

Bit 0 No TorqueLimit if TorquemodeOn

From version 12.00.00 onwards

: If sensorless vector

control (

SLVC

) or servo control (

SC

) are used, in the

"torque control with speed limitation" mode the torque

limitation via nTorqueMotLimit_a and

nTorqueGenLimit_a is also active to limit the torque

setpoint.

• If you want to deactivate the torque limitation to

retain the former function, set bit 0 to "1".

Bit 1 250ms IMP before DCB
Bit 2 1000ms IMP before DCB
Bit 3 DCB: Current controller and C036

app. to C088

Bit 4 Motorident.: No calculation C73 C75

C76 C77 C78

From version 12.00.00 onwards

: Following successful

motor parameter identification, the current controller

and field controller parameters are calculated as well.

• If these parameters are not to be calculated, bit 4

must be set to "1".

Automatic motor data identification

Bit 5 Motorident.: Calculation C70 C71

C72

From version 12.00.00 onwards

: Following successful

motor parameter identification, the speed controller

parameters can automatically be calculated as well.

• If these parameters are to be calculated, bit 5 must be

set to "1".

Automatic motor data identification

Bit 6 Motorident.: Calculation C11 C22

C497 C966 C982

From version 12.00.00 onwards

: Following successful

motor parameter identification, further controller

parameters can be calculated automatically.

• If these parameters are to be calculated, bit 6 must be

set to "1".

Automatic motor data identification

Bit 7 Reserved
Bit 8 DC-bus supply with DC charging

connection

Bit 9 Inverter characteristics inactive

Bit 10 SCPSM: Extrapolation - actual speed

value inactive

Bit 11 TopLine: Speed encoder signal cycle

500us

Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved

Subcodes

Lenze setting

Info

C02865/1

0x0000

MCTRL

: Special settings

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT