CANopen option

11.11

Implemented CANopen objects | I-1016

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

I-1016

Monitoring time for the nodes to be monitored via heartbeat.

Heartbeat protocol

( 672)

• The parameterised time is rounded down to an integer multiple of 5 ms and must have a greater

value than the heartbeat producer time of the node to be monitored.

[11-4] Data telegram assignment

Index:

I-1016

Name:

Consumer heartbeat time

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Highest subindex supported

1 (for BaseLine)

7 (for StateLine)

15 (for HighLine)

- (read access only)

ro

U16

1 ... n: Consumer heartbeat time

0

0

65535 rw

U16

Subindex

Meaning

Lenze code

0

Number of nodes to be monitored

1 ... n

Node ID and heartbeat time of the node to be monitored Node ID:

C00385/x

Heartbeat time:

C00386/x

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31 ... bit 24

Bit 23 ... Bit 16

Bit 15 ... Bit 0

0

(Reserved)

Node ID

Heartbeat time

in [ms]