756

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00066

C00070

C00071

C00072

Parameter | Name:

C00066 | Thermal motor load (I²xt)

Data type: INTEGER_16

Index: 24509

d

= 5FBD

h

Display of the thermal motor load, sensorlessly determined using a motor model

• If the value displayed here exceeds "100.00 %", the error message "OC6: Thermal motor overload (I2xt)" is output

and the fault response set in

C00606

is executed (default setting: "Warning").

Motor overload monitoring (I2xt)

Display range

(min. value | unit | max. value)

0.00

%

199.99

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00070 | Vp speed controller

Data type: UNSIGNED_16

Index: 24505

d

= 5FB9

h

Amplification factor Vp of the speed controller for different motor control modes
Setting range

(min. value | unit | max. value)

0.00

600.00

Subcodes

Lenze setting

Info

C00070/1

15.00

SLVC

: Vp speed controller

C00070/2

6.00

SC

: Vp speed controller

C00070/3

3.00

SLPSM: Vp speed controller

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00071 | Ti speed controller

Data type: UNSIGNED_16

Index: 24504

d

= 5FB8

h

Reset time Ti of the speed controller for different motor control modes
Setting range

(min. value | unit | max. value)

0.0

ms

6000.0

Subcodes

Lenze setting

Info

C00071/1

100.0 ms

SLVC

: Ti speed controller

C00071/2

50.0 ms

SC

: Ti speed controller

C00071/3

100.0 ms

SLPSM: Ti speed controller

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00072 | SC: Tdn speed controller

Data type: UNSIGNED_16

Index: 24503

d

= 5FB7

h

Differential time constant Tdn of the speed controller for servo control (

SC

)

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

ms

3.00 0.00 ms

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Advertising