Oc6: i2xt motor overload, Oc6: i2xt overload motor, Error message – Lenze 8400 User Manual

Page 597: Lp1: motor phase failure, Xx.0123.00099, Xx.0123.00145, Xx.0123.00105, Xx.0123.00098, Xx.0123.00200, 9diagnostics & error management

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

597

9

Diagnostics & error management

9.10

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

oC16: Torque controller limitation [xx.0123.00098]

FC03: Field controller limitation [xx.0123.00099]

oC6: I2xt overload - motor [xx.0123.00105]

LP1: Motor phase failure [xx.0123.00145]

Sd10: Speed limit - feedback system 12 [xx.0123.00200]

Response (Lenze setting printed in bold)

Setting:

C00570/3

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Actuator limitation according to speed controller.

• Observe load requirements.

• Correct dimensioning or reduce setpoint generation

dynamics if necessary.

Motor control

Response (Lenze setting printed in bold)

Setting:

C00570/4

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The output of the field controller has reached its

maximum limit value. The drive is at the torque limit in

the field weakening range.

• Observe load requirements.

• Correct dimensioning or reduce setpoint from the

field weakening range if necessary.

Motor control

Response (Lenze setting printed in bold)

Setting:

C00606

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Thermal overload of the motor.

Only self-ventilated motors can be monitored using the

I2xt function.

• Check whether is it a self-ventilated motor. If not, set

C00606

to "0: No Reaction".

• Observe load requirements.

• Correct dimensioning if necessary.

• For VFCplus control type: Check Vmin boost (

C00016

).

Set Vmin boost

Response (Lenze setting printed in bold)

Setting:

C00597

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Motor phase failure - power section

• This error message is displayed if a motor phase

carries less current of one half-wave than set in

C00599

.

• Check the motor connections and the corresponding

plug connector on the device and, if necessary, the

motor terminal box.

• Check the trigger threshold (

C00599

).

Response (Lenze setting printed in bold)

Setting:

C00607

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Maximally permissible speed of the feedback system

connected to DI1/DI2 reached.

Reduce speed of the rotation shaft/feedback system.

n

encoder

<= (f

max

x 60) / encoder increment

(for f

max

= 10 kHz)