Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

283

5

Motor control (MCTRL)

5.14

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Adjustment of the motor utilisation meter
The motor utilisation meter for indicating the motor load in

C00066

begins to count when the

apparent motor current (

C00054

) is greater than the motor overload setting (

C00120

).

The Motor overload setting (

C00120

) is calculated as follows:

• If you reduce

C00120

starting from the calculated value, the motor utilisation meter will already

be counted up before the rated overload threshold is reached.

• If you increase

C00120

starting from the calculated value, the motor utilisation meter will not

be counted up until the rated overload threshold is reached.

[5-34] Tripping characteristic of the I

2

xt monitoring

Note!

From version 07.00.00

, the thermal motor load displayed in

C00066

can be pre-

initialised when the device is connected to the mains, optionally using a fixed value or

the value used last at the time when the device was switched off. The desired

initialisation is selected in

C00122

. In the Lenze setting of

C00122

, the behaviour

remains unchanged (no initialisation).

f: Output frequency

t: Release time

I

N

: Rated current of drive controller at a switching frequency of f = 8 kHz

I

r

: Rated motor current (see nameplate of motor)

C00054

: Apparent motor current

C00120

: Motor overload setting

C00120

Rated motor current (C00088)

Rated device current (C00098)

------------------------------------------------------------------------------

100 %

=

60

180

240

300

360

t [s]

0.5

0

0

1.0

1.5

2.0

C00054

I

r

120

f = 0 Hz

f = 20 Hz

f > 40 Hz

I x 100 %

I

r

N

C00120 <

I x 100 %

I

r

N

C00120 =

I x 100 %

I

r

N

C00120 >