5

Motor control (MCTRL)

5.10

Parameterisable additional functions

244

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Lowering of the switching frequency depending on the output current
"Variable" switching frequencies can be selected for the controller in

C00018

, where the controller

automatically lowers the switching frequency depending on the controller output current. The

modulation mode will not be changed.

When a "fixed" switching frequency is selected, no switching frequency changeover takes place. In

case of fixed frequencies, the controller output current is limited to the permissible value of the

corresponding switching frequency. In case of larger load impulses, the overcurrent interruption

may be activated, to which the controller responds with "Error".

Limiting the maximum output frequency

The maximum output frequency (

C00910

) of the controller is not limited depending on the

switching frequency. Therefore, adapt the maximum output frequency according to our

recommendation:

• At a switching frequency of 4 kHz, for instance, 500 Hz for the maximum output frequency

should not be exceeded.

Carry out further measures:

• If required, deactivate the switching frequency changeover by the heatsink temperature via

C00144

.

• If required, ensure that the changeover threshold of the controller output current to the next

switching frequency below will not be exceeded. If required, select a constant switching

frequency in

C00018

.

Operation at an ambient temperature of 45°C
The controller is designed so that operation at an ambient temperature of 45° C without derating is

permissible at a switching frequency of 4 kHz.

The switching thresholds are given in the rated data in the 8400 protec hardware

manual.

• The hardware manual has been stored in electronic form on the data carrier supplied

with the 8400 drive controller.

Note!

If the servo control mode (SC) is selected, the drive assumes the 'maximum current

limitation' state if the maximum output frequency (

C00910

) has been reached.

Defining current and speed limits

( 145)

Maximum output frequency 1

8

---