5motor control (mctrl) – Lenze 8400 User Manual

Page 267

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

267

5

Motor control (MCTRL)

5.11

Encoder/feedback system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Short overview of the relevant parameters:

How to parameterise the SSI encoder:

1. As encoder type (

C00422

), select "4: Absolute value encoder (SSI)".

2. Set the bit rate (

C00427

) for SSI communication.

• For SSI protocols, the permissible baud rate is reduced if the cable length is increased. A

safe bit rate must be set, depending on the length of the used encoder cable and the

electromagnetic interference level.

3. Go to

C00426/1...6

and set the distribution of the SSI data word according to the SSI

encoder used (see the following subchapter).

4. If an SSI encoder with Gray coding is used:

Add the selection "1: Gray code" for a data conversion from Gray to binary code in

C00428

.

• In the Lenze setting, "0: Binary code", conversion is not performed, i.e. an SSI encoder

with binary coding is expected.

Parameter

Info

Lenze setting

Value Unit

General

C00428

SSI encoder: Coding

0: Binary code

C00427

SSI encoder: Bit rate

1: 100 kbps

Structure of the data word

C00426/1

Data word length

25

C00426/2

Bits Singleturn

13

C00426/3

Start bit singleturn

0

C00426/4

Bits multiturn

12

C00426/5

Start bit multiturn

13

Advertising