5 pole position identification without motion, Pole position identification without motion, Oided – Lenze 8400 User Manual

Page 214: Pole, Position identification without motion, 5motor control (mctrl)

Advertising
background image

5

Motor control (MCTRL)

5.8

Sensorless control for synchronous motors (SLPSM)

214

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.8.5

Pole position identification without motion

When sensorless control is active for synchronous motors (SLPSM), the rotor displacement angle is

identified with every controller enable in the Lenze setting and thus a jerk in the machine after

controller enable can be avoided.
The "Pole position identification without motion" is able to identify the electrical rotor

displacement angle with an accuracy of up to 10°. The identification takes 1 ... 15 ms depending on

the motor. The function is preset in the Lenze setting so that no further settings need to be made in

the majority of cases. In order to get the same behaviour as before, the function can be deactivated

in

C02874

.

Short overview of the relevant parameters:

• The stator time constants can be calculated based on the following formula:

Parameter

Info

Lenze setting

Value Unit

C02874

Pole position identification

1: On

C02872

PLI: Adaptation of time period PLI in operation

0

C02875

PLI: Adaptation of ident angle PLI in operation

0 °

C02870

PLI: Degree of optimisation

- %

C02871

PLI: Identification time

- ms

C02873

PLI: Identified rotor displacement angle

- °

Highlighted in grey = display parameter

Note!

In case of synchronous motors with a stator time constant < 1 ms, the pole position

identification is not executed since the resulting test current pulse could exceed the

permissible motor current.

• This, however, only affects very few synchronous motors with very low power (e.g.

Lenze motor MDSKS-020-13-300 with rated power of 40 W).

• A non-executed pole position identification can be recognised by the display

C02870

= 0 % and

C02871

= 0 ms.

T

S

= stator time constant

L

ss

= Motor stator leakage inductance (

C00085

)

R

s

= Motor stator resistance (

C00084

)

T

s

[ms]

L

ss

[mH]

R

s

Ω

[ ]

--------------------

=