C01121 | sync cycle time setpoint, C01122 | sync phase position, C01123 | sync window – Lenze 8400 User Manual

Page 989: C01121, Selected in, C01122, C01123, Rmining, The poin, 16 parameter reference

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

989

16

Parameter reference

16.2

Parameter list | C01121

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C01121

C01122

C01123

Parameter | Name:

C01121 | Sync cycle time setpoint

Data type: UNSIGNED_16

Index: 23454

d

= 5B9E

h

Cycle time setpoint for device synchronisation

• Time interval at which the phase control loop (PLL) in the controller expects the synchronisation signals.

• The cycle time setpoint must be set according to the cycle of the respective synchronisation source.

Note:

• Only integer multiples of 1000 μs can be set.

• Intelligent communication modules usually define the cycle time setpoint derived from the bus cycle. In this

case, a manual change is not possible.

Example: For the CAN bus, a distance of 2 ms has been set between two synchronisation signals. If the CAN bus is

to be used as synchronisation source, a synchronisation cycle of 2000 μs must be set in C01121.
Setting range

(min. value | unit | max. value)

Lenze setting

1000

μs

20000 1000 μs

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01122 | Sync phase position

Data type: UNSIGNED_16

Index: 23453

d

= 5B9D

h

Phase position for device synchronisation

• The phase position determines the zero-time of the internal system cycle with regard to the synchronisation

signal (bus cycle). Since PDO processing is an inherent part of the system part of the application, the instant of

acceptance of the PDOs is postponed as well by a changed phase position.

• With a setting = 0, the system cycle starts simultaneously with the synchronisation signal.

• With a setting > 0, the internal system cycle starts earlier by the set time with regard to the synchronisation

signal (the phase position acts negatively).

• Intelligent communication modules define the optimal time with activated synchronisation by themselves. In

this case, a manual change is not possible.

• The decisive factor for defining C01122 is the time where all nodes are provided with valid PDOs.

Example: If the phase position is set to 550 μs, the system part of the application starts 550 μs before the arrival of

the synchronisation signal.
Setting range

(min. value | unit | max. value)

Lenze setting

0

μs

1000 0 μs

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01123 | Sync window

Data type: UNSIGNED_16

Index: 23452

d

= 5B9C

h

Time slot for monitoring the synchronisation signal or the phase position

• The synchronisation signal or the current phase position must be within this time slot around the corresponding

expected value (

C01122

).

• With the setting "1000 μs" there will be no monitoring.

Setting range

(min. value | unit | max. value)

Lenze setting

0

μs

10000 100 μs

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Advertising