2 analog terminals, Analog terminals, 6i/o terminals – Lenze 8400 User Manual

Page 326

Advertising
background image

6

I/O terminals

6.2

Analog terminals

326

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.2

Analog terminals

The controller is provided with two analog input terminals (O1U and O1I) at the socket X50 for

detecting a current or voltage signal.

• Voltage signal in the 0 ... + 10 V range

The voltage signal can be e.g. an analog speed setpoint selection or the signal of an external

sensor (temperature, pressure, etc.).

• Current signal in the 0/+ 4 ... + 20 mA range

For open-circuit monitoring, the current signal can be evaluated with regard to "Life Zero" or

"Dead Zero":

• 0 ... 20 mA, without open-circuit monitoring
• 4 ... 20 mA, with open-circuit monitoring

Parameterisation dialog in the »Engineer«:

Short overview of the parameters for the analog input:

Related topics:

User-defined terminal assignment

( 339)

Note!

To avoid undefined states, unassigned inputs of the controller must be assigned as well,

e.g. by applying 0 V to the terminal.

Button

Function

Parameterising analog input ( 327)

Open the parameterising dialog for assigning application inputs to the analog input.

Changing the terminal assignment with the »Engineer« ( 343)

Parameter

Info

Lenze setting

Value Unit

Analog input 1

C00028/1

AIN1: Input voltage

- V

C00029/1

AIN1: Input current

- mA

C00033/1

AIN1: Output value (to application)

- %

Highlighted in grey = display parameter