C00446 | freqinxx_nout_a, C00447 | digout decoupling, C00446/1 – Lenze 8400 User Manual

Page 829: C00446/2, C00447, 16 parameter reference

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

829

16

Parameter reference

16.2

Parameter list | C00446

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00446

C00447

Parameter | Name:

C00446 | FreqInxx_nOut_a

Data type: INTEGER_16

Index: 24129

d

= 5E41

h

Display of the frequency input signals which are fed into the application.

Using DI1(5) and DI2(6) as frequency inputs

Display range

(min. value | unit | max. value)

-199.99

%

199.99

Subcodes

Info

C00446/1

FreqIn12_nOut_a

C00446/2

FreqIn56_nOut_a

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00447 | DigOut decoupling

Data type: UNSIGNED_16

Index: 24128

d

= 5E40

h

From version 02.00.00

Configuration defining the events that lead to a decoupling of the digital output terminals.

Configuring exception handling of the output terminals

Setting range

(min. hex value | max. hex value)

Lenze setting

0x0000

0xFFFF 0x0000 (decimal: 0)

Value is bit-coded: (= bit set)

Bit 0  SafeTorqueOff
Bit 1  ReadyToSwitchOn
Bit 2  SwitchedOn
Bit 3  Reserved
Bit 4  Trouble
Bit 5  Fault
Bit 6  Reserved
Bit 7  Reserved
Bit 8  Reserved
Bit 9  Fail CAN_Management

Bit 10  Reserved
Bit 11  Reserved
Bit 12  Reserved
Bit 13  Reserved
Bit 14  Reserved
Bit 15  Reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT