8.6

Homing

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Mode 13: <_Ln

Procedure:

1. Movement in negative direction with start profile data set.
2. Positive edge of the travel range limit switch sets reference.

 Negative travel range limit switch

Mode 13

<

Ln

Offset path

Sequence profile (optional)

Start speed

Profile speed

Lp

Inactive

Inactive

Active

Active

Ln

Inactive

Inactive

Inactive

Active

Note!

The load machine can also leave the travel range limit switch. There follows a return to

the home position that was set with the positive edge of the travel range limit switch.

• It is possible that, as a result, the machine will remain on an operated limit switch.
• It is therefore recommended that a home value offset be set in

C01227/1

in order to

release the operated limit switch.