C00364 | can messageerror, C00366 | number of can sdo channels, T in – Lenze 8400 User Manual

Page 815: C00366, 16 parameter reference

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

815

16

Parameter reference

16.2

Parameter list | C00364

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00364

C00366

Parameter | Name:

C00364 | CAN MessageError

Data type: UNSIGNED_8

Index: 24211

d

= 5E93

h

CANopen Option/CAN on board

Selection list

(read only)

0 No Error
1 StuffError
2 FormError
3 AckError
4 Bit1Error
5 Bit0Error
6 CRCError
7 Reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00366 | Number of CAN SDO channels

Data type: UNSIGNED_8

Index: 24209

d

= 5E91

h

Selection of the number of active parameter data channels

• In the Lenze setting, according to CANopen only parameter data channel 1 is activated.

• To activate both parameter data channels, set the selection "2 SDO Lenze".

CANopen Option/CAN on board

Selection list

(Lenze setting printed in bold)

0 1 SDO CANOpen
1 2 SDO Lenze

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1