Function library
18.1
Function blocks | L_MPot_1
1316
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
18.1.102.2 Deactivate motor potentiometer
When the motor potentiometer is deactivated by setting bInAct to TRUE, the nOut_a output signal
responds according to the function selected via Function.
[18-44] Example: Deactivation of the motor potentiometer when the Function = 1 has been selected
When the motor potentiometer is deactivated, nOut_a is reduced to 0 % with the deceleration time wTif.
If it is activated again, nOut_a is increased again to nLowLimit with the acceleration time wTir.
nOut_a
t
t
TRUE
FALSE
bUp
t
TRUE
FALSE
bDown
nHighLimit
nLowLimit
0
wTir
wTif
wTir
t
TRUE
FALSE
bInAct
wTif
wTif
0