C00077

C00078

C00079

Parameter | Name:

C00077 | SC: Vp field controller

Data type: UNSIGNED_16

Index: 24498

d

= 5FB2

h

Gain factor Vp of the field controller for servo control (

SC

)

• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered

automatically.

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

500.00 12.80

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00078 | SC: Tn field controller

Data type: UNSIGNED_16

Index: 24497

d

= 5FB1

h

Reset time Tn of the field controller for servo control (

SC

)

• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered

automatically.

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

ms

6000.0 256.0 ms

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00079 | SC: Settings

Data type: UNSIGNED_8

Index: 24496

d

= 5FB0

h

Configuration of different options for servo control (

SC

)

Selection list

0 Off
1 On

Subcodes

Lenze setting

Info

C00079/1

0: Off

SC

: Current controller - feedforward control

• Feedforward control/decoupling network of the

current controller.

C00079/2

1: On

SC

: Adapt. field weakening controller

• Speed-dependent adaptive field weakening

controller.

C00079/3

0: Off

SC

: n-ctrl anti-wind-up

• "Anti-wind-up" effect of the speed controller in case

of an output voltage limitation in the field weakening

range.

C00079/4

1: On

Field weakening for synchronous motors

From version 12.00.00

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1