C00227 | l_pctrl_1: acceleration time, C00228 | l_pctrl_1: deceleration time, C00231 | l_pctrl_1: operating range – Lenze 8400 User Manual

Page 794: C00233 | l_pctrl_1: root function, C00227, C00228, C00233, 16 parameter reference

Advertising
background image

16

Parameter reference

16.2

Parameter list | C00227

794

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00227

C00228

C00231

C00233

Parameter | Name:

C00227 | L_PCTRL_1: Acceleration time

Data type: UNSIGNED_32

Index: 24348

d

= 5F1C

h

The

L_PCTRL_1

FB: Acceleration time for the output value of the PID process controller

Setting range

(min. value | unit | max. value)

Lenze setting

0.000

s

999.999 0.010 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00228 | L_PCTRL_1: Deceleration time

Data type: UNSIGNED_32

Index: 24347

d

= 5F1B

h

The

L_PCTRL_1

FB: Deceleration time for the output value of the PID process controller

Setting range

(min. value | unit | max. value)

Lenze setting

0.000

s

999.999 0.010 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00231 | L_PCTRL_1: Operating range

Data type: INTEGER_16

Index: 24344

d

= 5F18

h

The

L_PCTRL_1

FB: Operating range for the PID process controller

Setting range

(min. value | unit | max. value)

0.00

%

199.99

Subcodes

Lenze setting

Info

C00231/1

199.99 %

L_PCTRL_1

: Pos. maximum

C00231/2

0.00 %

L_PCTRL_1

: Pos. minimum

C00231/3

0.00 %

L_PCTRL_1

: Neg. minimum

C00231/4

199.99 %

L_PCTRL_1

: Neg. maximum

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00233 | L_PCTRL_1: Root function

Data type: UNSIGNED_8

Index: 24342

d

= 5F16

h

The

L_PCTRL_1

FB: Use of the root function at the actual value input

Selection list

(Lenze setting printed in bold)

Info

0 Off

Root function inactive

• The actual value nAct_a remains unchanged for

further processing

1 On

Root function active

• The root is extracted of the actual value nAct_a for

further processing

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1