7technology applications – Lenze 8400 User Manual

Page 380

Advertising
background image

7

Technology applications

7.3

TA "Table positioning"

380

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

nTorqueMotLim_a

nTorqueGenLim_a

INT

Torque limitation in motor mode and in generator mode

• These input signals are directly transferred to the motor control to limit the

controller's maximum torque in motor and generator mode.

• The drive cannot output a higher torque in motor/generator mode than set here.

• The applied values (any polarity) are internally interpreted as absolute values.

• If V/f characteristic control (VFCplus) is selected, limitation is indirectly

performed via a so-called I

max

controller.

• If sensorless vector control (SLVC) or servo control (SC) is selected, limitation has

a direct effect on the torque-producing current component.

• Scaling: 16384 ≡ 100 % M

max

(

C00057

)

Note:

Setting this input is ineffective in the reference modes 14 and 15 ("Homing to

positive stop").
Torque limits in motor and generator mode:

bSetSpeedCcw

BOOL

Change of direction of rotation

• For instance if a motor or gearbox is fixed laterally reversed to a machine part, but

the setpoint selection should still be executed for the positive direction of

rotation.

FALSE Clockwise rotation (Cw)

TRUE Direction of rotation to the left (Ccw)

nMainSetValue_a

INT

Main speed setpoint

• Offset and gain of this input signal can be set in

C00696

and

C00670

for a simple

signal adjustment of a setpoint encoder.

• Scaling: 16384 ≡ 100 % reference speed (

C00011

)

• The main setpoint is transformed to a speed setpoint in the setpoint encoder via

a ramp function generator with linear or S-shaped ramps.

• Upstream to the ramp function generator, a blocking speed masking function

and a setpoint MinMax limitation are effective.

• For a detailed functional description see the

L_NSet

FB.

nAuxSetValue_a

INT

Additional speed setpoint

• Offset and gain of this input signal can be set in

C00697

and

C00671

for a simple

signal adjustment of a setpoint encoder.

• Scaling: 16384 ≡ 100 % reference speed (

C00011

)

• The additional speed setpoint can be linked arithmetically with the main speed

setpoint behind the ramp function generator.

• The additional speed setpoint can be shown via ramp times of a second ramp

function generator.

• For a detailed functional description see the

L_NSet

FB.

bJogSpeed1

bJogSpeed2

BOOL

Selection inputs for fixed changeover setpoints (JOG setpoints) for the main setpoint

• Selection inputs are binary coded.

Identifier

Data type

Information/possible settings

n

N

M

N

M

-M

N

-n

N

n

TorqueMotLim

TorqueGenLim

TorqueMotLim

TorqueMotLim

TorqueGenLim