C00597 | resp. to motor phase failure, C00598 | resp. to i/o monitoring, C00599 | motor phase failure threshold – Lenze 8400 User Manual

Page 855: C00597, C00599, Will take place, N error response is set in, C00598, C00598/1, C00598/2

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

855

16

Parameter reference

16.2

Parameter list | C00597

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00597

C00598

C00599

Parameter | Name:

C00597 | Resp. to motor phase failure

Data type: UNSIGNED_8

Index: 23978

d

= 5DAA

h

Response to motor phase failure

• If a phase current does not exceed the threshold set in

C00599

for more than one period, the response set here

will be triggered.

Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
5 Warning

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00598 | Resp. to I/O monitoring

Data type: UNSIGNED_8

Index: 23977

d

= 5DA9

h

Configuration of monitoring of the analog inputs

Analog terminals

Selection list

0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
5 Warning

Subcodes

Lenze setting

Info

C00598/1

3: TroubleQuickStop

Response to open circuit at AIN1 if configured as

4 ... 20 mA current loop

C00598/2

3: TroubleQuickStop

Response to open circuit at AIN2 when being configured

as 4 ... 20 mA-current loop

C00598/3

5: Warning

Resp. to digital output level

C00598/4

5: Warning

Resp. to IO supply overload

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00599 | Motor phase failure threshold

Data type: INTEGER_16

Index: 23976

d

= 5DA8

h

Threshold for motor phase failure monitoring

• 100 % ≡ rated inverter current (

C00098

)

• If a phase current does not exceed the threshold set here for more than one period, the response to motor phase

failure set in

C00597

will be triggered.

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

100.00 5.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100