2 setting the error response, Setting the error response, 9diagnostics & error management – Lenze 8400 User Manual

Page 575

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

575

9

Diagnostics & error management

9.7

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.7.2

Setting the error response

When a monitoring function responds, the response set for this monitoring function (TroubleQSP,

Warning, Fault, etc.) will be triggered.

• For many monitoring functions the response can be individually parameterised via parameters.

Tip!
The table in the chapter "

Short overview (A-Z)

" contains the error messages for which the

response can be set.

( 586)

Warning thresholds
Some of the monitoring functions are activated if a defined warning threshold (e.g. temperature)

has been exceeded.

• The corresponding preset threshold values can be changed via the following parameters:

Parameter

Info

C00120

Setting of motor overload (I²xt)

C00123

Device utilisat. threshold (Ixt)

C00572

Brake resistor overload threshold

C00599

Motor phase failure threshold

Advertising