Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

411

7

Technology applications

7.4

TA "Switch-off positioning"

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Outputs

GP: GeneralPurpose

The following inputs are interconnected with logic/arithmetic functions on application level for free usage.

"GeneralPurpose" functions

nGPAnalogSwitchIn1_a

nGPAnalogSwitchIn2_a

INT

Analog switch

: Input signals

• The input signal selected via the selection input bGPAnalogSwitchSet is output at

output nGPAnalogSwitchOut_a.

bGPAnalogSwitchSet

BOOL

Analog switch

: Selection input

FALSE nGPAnalogSwitchOut_a = nGPAnalogSwitchIn1_a

TRUE nGPAnalogSwitchOut_a = nGPAnalogSwitchIn2_a

nGPArithmetikIn1_a

nGPArithmetikIn2_a

INT

Arithmetic

: Input signals

• The arithmetic function is selected in

C00338

.

• The result is output at output nGPArithmetikOut_a.

nGPMulDivIn_a

INT

Multiplication/Division

: Input signal

• The factor for the multiplication can be set in

C00699/1

(numerator) and

C00699/2

(denominator).

• The result is output at output nGPMulDivOut_a.

bGPDigitalDelayIn

BOOL

Binary delay element

: Input signal

• The on-delay can be set in

C00720/1

.

• The off-delay can be set in

C00720/2

.

• The time-delayed input signal is output at output bGPDigitalDelayOut.

bGPLogicIn1

bGPLogicIn2

bGPLogicIn3

BOOL

Binary logic

: Input signals

• The logic operation is selected in

C00820

.

• The result is output at output bGPLogicOut.

nGPCompareIn1_a

nGPCompareIn2_a

INT

Analog comparison

: Input signals

• The comparison operation is selected in

C00680

.

• Hysteresis and window size can be set in

C00680

and

C00682

.

• If the comparison statement is true, the output bGPCompareOut will be set to

TRUE.

bGPDFlipFlop_InD

bGPDFlipFlop_InClk

bGPDFlipFlop_InClr

BOOL

D-FlipFlop

: Input signals

• Data, clock and reset input

Free inputs

The following inputs can freely be interconnected on the application level.

The signals can be transferred from the I/O level to the application level via these inputs.
bFreeIn1 ... bFreeIn8

BOOL

Free inputs for digital signals

wFreeIn1 ... wFreeIn4

WORD

Free inputs for 16-bit signals

dnFreeIn1_p ... dnFreeIn2_p

DINT

Free inputs for 32-bit signals

Identifier

Data type

Value/meaning

wDriveControlStatus

WORD

Status word of the controller

• The status word contains information on the currents status of the drive

controller.

• See the "

wDeviceStatusWord status word

" subchapter of the chapter on device

control for a detailed description of the bit assignment.

wStateDetermFailNoLow

WORD

Display of the status determining error (LOW word)

Identifier

Data type

Information/possible settings