16

Parameter reference

16.2

Parameter list | C00123

768

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00123

C00129

C00130

C00131

C00133

Parameter | Name:

C00123 | Device utilisation threshold (Ixt)

Data type: INTEGER_16

Index: 24452

d

= 5F84

h

Operating threshold for the "OC5: Device overload (Ixt)" error message

• The current device utilisation is displayed in

C00064

.

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

150.00 150.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00129 | Brake resistance value

Data type: UNSIGNED_16

Index: 24446

d

= 5F7E

h

Resistance value of the connected brake resistor

• The value to be entered can be obtained from the nameplate of the brake resistor.

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

Ohm

500.0 39.0 Ohm

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00130 | Rated power - brake resistor

Data type: UNSIGNED_16

Index: 24445

d

= 5F7D

h

Rated power of the connected brake resistor

• The value to be entered can be obtained from the nameplate of the brake resistor.

Setting range

(min. value | unit | max. value)

Lenze setting

0

W

65535 100 W

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00131 | Thermal capacity - brake resistor

Data type: UNSIGNED_16

Index: 24444

d

= 5F7C

h

Thermal capacity of the connected brake resistor

• The value to be entered can be obtained from the nameplate of the brake resistor.

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

kWs

6553.5 10.0 kWs

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00133 | Brake resistor utilisation

Data type: UNSIGNED_16

Index: 24442

d

= 5F7A

h

Display of the utilisation of the connected brake resistor
Display range

(min. value | unit | max. value)

0

%

65535

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1