Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

287

5

Motor control (MCTRL)

5.14

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Temperature model

[5-35] Signal flow for monitoring the brake resistor

The monitoring function calculates the braking current I

Br

from the current DC-bus voltage U

DC_act

and the brake resistance parameterised in

C00129

:

• The calculation considers the thermal utilisation of the brake resistor based on the following

parameters:

• Resistance value (

C00129

)

• Continuous power (

C00130

)

• Thermal capacity (

C00131

)

• In the Lenze setting these parameters are preset with the corresponding power-adapted Lenze

brake resistor.

C00133

indicates the calculated utilisation of the brake resistor in [%].

• A utilisation of 100 % corresponds to the continuous power of the brake resistor depending

on the maximally permissible temperature limit.

Related topics:

Braking operation/brake energy management

( 270)

Error message: "

oC12: I2xt overload brake resistor

"

J

C00138

C00130
C00131

I

Br

I

= 1

On

I

= 0

Off

I xt

2

C00572

C00574

C00129

)

Temperature model

Note!

The monitoring function can also be triggered due to a value entered in

C00129

although a brake resistor is not even connected.

I

Br

U

DC_act