2 setting the baud rate, 3 setting the node address, Setting the baud rate – Lenze 8400 User Manual

Page 634: Setting the node address, 11 canopen option

Advertising
background image

11

CANopen option

11.2

Possible settings via DIP switch

634

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

11.2.2

Setting the baud rate

The baud rate can be set via code

C00351

or with the DIP switches a to d:

11.2.3

Setting the node address

The node address can be set via code

C00350

or with the DIP switches 1 to 64.

• The labelling on the housing corresponds to the values of the individual DIP switches for

determining the node address.

• The valid address range depends on the number of SDO channels set in

C00366

:

• 1 SDO (Lenze setting): 1 ... 127
• 2 SDO: 1 ... 63

Example: Setting of the node address 23

Note!

• All DIP switches (a ... d, 1 ... 64) = OFF (Lenze setting):

• At switching on, the settings under code

C00350

(node address) and

C00351

(baud

rate) will become active.

• Preset baud rate: 500 kbps

DIP switch position

Baud rate

d

c

b

a

OFF

OFF

ON

ON

50 kbps

OFF

OFF

ON

OFF

125 kbps

OFF

OFF

OFF

ON

250 kbps

OFF

OFF

OFF

OFF

500 kbps

ON

ON

ON

OFF

800 kbps (only effective from "HighLine" onwards)

OFF

ON

OFF

OFF

1000 kbps (only effective from "HighLine" onwards)

Note!

• The addresses of the nodes must differ from each other.
• All DIP switches (a ... d, 1 ... 64) = OFF (Lenze setting):

• At switching on, the settings under code

C00350

(node address) and

C00351

(baud

rate) will become active.

DIP switch

64

32

16

8

4

2

1

Switch position

OFF

OFF

ON

OFF

ON

ON

ON

Value

0

0

16

0

4

2

1

Node address

= Sum of the values = 16 + 4 + 2 + 1 = 23